AI model training and inference workloads can cause significant fluctuations in server loads, placing far more stringent demands on data center power supplies than traditional servers in terms of output power, power density, conversion efficiency, transient response, and hold-up time. Within the OCP ORv3 specification framework, 12 kW-class PSUs are becoming essential hardware for next-generation AI computing racks.
Infineon's application note AN133110 provides a comprehensive reference design for a 12 kW high-frequency, high-power-density power supply targeting AI data centers and servers.
Download Link: https://cdn-files.myshopline.com/file/store/1764745930772/infineon-12kw-high-power-density-and-high-frequency-psu-for-ai-data-centers-and-servers-applicationnotes-en-pdf20261008.pdf
The design adopts a two-stage power conversion architecture consisting of a three-level flying-capacitor interleaved totem-pole PFC + full-bridge LLC resonant converter, supplemented by an auxiliary energy-buffering circuit. It delivers a rated output of 12 kW within a compact overall form factor of 40 mm × 68 mm × 640 mm. The document provides detailed coverage of topology selection, component selection, hardware implementation, protection logic, and experimental test results, including efficiency, thermal performance, EMI, and dynamic load response. It serves as an important engineering reference for developers of AI server power supplies.